VESDA-E

 

Introducing Vesda-E Video:

 

 

How VESDA works?

VESDA, World’s No. 1 ASD Brand, works by continuously drawing air into a distributed pipe network via a high-efficiency aspirator. The air sample then passes through a dual-stage filter. The first stage removes dust and dirt from the air sample before it enters the CMOS detection chamber. The second, ultra-fine stage provides an additional clean-air supply to keep the detector’s optical surfaces free from contamination, ensuring stable calibration and long detector life as well as minimizing nuisance alarms. From the filter, the air sample goes through the calibrated detection chamber where it is exposed to a CMOS light source. When smoke is present, light is scattered within the detection chamber and is instantly identified by the highly sensitive receiver system. The signal is then processed and presented via a bar-graph display, alarm threshold indicators and/or graphic display. VESDA detectors are able to communicate this information to a fire alarm control panel, a software management system, or a building management system via relays or a High Level Interface (HLI).